What happened
On 20 November 2026, the BBC reported a UK operation against exposed refrigeration controllers. Since late October, researchers, operators, the National Cyber Security Centre, Defra and the Food Standards Agency had worked to remove Resource Data Management (RDM) controllers from the internet. The sites included supermarkets, warehouses, restaurants, petrol stations and stadiums. Warnings also went to hotels, food plants and cold stores.
According to the BBC, each of these devices can control dozens of fridges and freezers. Thousands were taken offline remotely. At some sites, staff removed the internet cable and then checked the temperatures by hand.
The UK operation was a precaution. RDM says that the issue was found in a test environment, that the first patches are deployed, and that there was no sign of malicious activity. RDM also says that an attack needs a piece of hardware. Pen Test Partners, who helped to raise the alarm, says that such hardware is cheap to buy online.
The BBC also listed three waves of attacks on refrigeration controllers in 2026:
- August: fridges at a small number of US military bases.
- 11 and 12 October: hundreds of supermarkets and food plants in France, where attackers targeted Danfoss temperature control systems.
- 1 and 2 November: dozens of supermarkets in seven European countries, most of all in Belgium and Luxembourg, and a small number of blood bank sites in France.
According to the BBC, the European waves spoiled large amounts of food.
What the vendors and the authorities say
On 17 November, Germany's Federal Office for Information Security (BSI) updated a warning about two products. The first is six vulnerabilities in Danfoss AK-SM 800A controllers on version 5.3.2. The BSI says that they can allow complete takeover of a device, permanent access, or a long denial of service. The second is 14 vulnerabilities in Copeland XWEB-EVO devices, which can give an attacker without a login full control (root rights). According to the BSI, sensors saw active attempts to exploit two of them (CVE-2026-124014 and CVE-2026-124010) soon after they were published.
On 20 November, Danfoss published two advisories:
- DSA-2026-12-01 (CVE-2026-127057): a buffer overflow that needs no login, on AK-SM 8xxA software version 5.4.0 and earlier. The fix comes in version 5.5.x. Until then, Danfoss says: keep the units off a public IP address, allow remote access only through a secure VPN or a protected network, switch on Strict mode, and use strong passwords.
- DSA-2026-12-02: weak or known passwords on the older AK-SC 355 and AK-SM 800 controllers, all versions. Danfoss gives the same access advice, and recommends a move to the current AK-SM 800A series so that the units keep getting updates.
The public record does not show that the October attacks used CVE-2026-127057. We know only what the public reports say. We do not comment on the investigations.
Why this matters for food, water and energy
A refrigeration controller holds the temperature of food, and sometimes of other sensitive stock. If an attacker can change a setpoint, start a defrost cycle or silence an alarm, the loss is physical and fast: spoiled stock, a stop in supply, and in the worst case a food safety problem.
Remote maintenance is normal. But "we have a service company" is not a security control. The problem is a management interface that anyone can reach from the internet. Often the path is a vendor modem or a 4G router that is not in any inventory.
Water and energy operators know this problem. From 15 years on the operator side in energy, we know how easy it is to miss a modem that a vendor or an integrator installed. A refrigeration controller on the internet is the same problem as a pump station PLC or a substation gateway on the internet.
There is one more lesson from the UK. When you cut a vendor's remote link without a plan, you can lose the monitoring that came through it. Some UK sites had to check temperatures by hand. That is the correct choice only if a person really watches the process.
The checklist
- List every controller with a management interface. Include refrigeration, process and telemetry controllers, and every unit that someone reaches through a vendor modem, a 4G or 5G router or a service company connection. If a contractor can reach it from their office, it is on the list. Write down the vendor, the model, the version and how someone reaches it today.
- Remove the direct internet path before you wait for a patch. If the interface has a public IP address, or a modem gives access to it, remove that path. Do this even if the firmware is current, the passwords are new or Strict mode is on.
- Allow remote access only through one maintained path. Use a VPN or a protected private network that you patch, log and can switch off. A list of the service company's addresses can be a short-term step. Agree the change with the vendor, so that the monitoring does not stop without anyone knowing.
- After the change, check the process, not only the network. Look for changes that you did not make: temperature setpoints, defrost schedules, alarm settings, user accounts and remote access settings. On a water or energy site, check setpoints, interlocks, alarm inhibits and engineering accounts. Treat each change that you cannot explain as an incident.
- Keep someone watching the process. Before you isolate a controller, agree who watches the temperatures or process values, how often, and how alarms reach a person who can act. Have this ready before you remove the cable.
- Plan for the whole fleet. Old controllers that get no more security updates, such as the units in the second Danfoss advisory, need a replacement plan and a date.
A first step for next week
You need one hour with the person who looks after the refrigeration or the process control, and one person from IT. You do not need to buy anything.
- Ask your main service companies and integrators one question in writing: "Which of our controllers can you reach from outside our site, and how?"
- Walk the plant room or the control panels and look for modems, 4G routers and SIM cards.
- Put both answers on one page: device, path, owner. Each path with no owner is your first task.
How this relates to NIS2
Food production, processing and distribution is a sector in NIS2. Water and energy are too. Article 21 asks for security in the supply chain, control of who has access to what, and incident handling. These measures apply to the controllers on the plant floor, not only to office IT. Whether your organisation is in scope depends on its size and on your national law. Check your national law.
Where to start
Do the one-hour list next week. Our free 30-point OT security checklist covers remote access and vendor connections in more detail, with no form to fill in. If you want a second opinion from the operator side on your list, a 30-minute call can settle what to fix first.
Sources:
- BBC News, "Tens of thousands of UK fridges secured from hackers in secret nationwide operation", 20 November 2026: bbc.co.uk
- Danfoss security advisories DSA-2026-12-01 (CVE-2026-127057) and DSA-2026-12-02, updated 20 November 2026: danfoss.com
- BSI, "Danfoss AK-SM800A & Copeland XWEB EVO: Zero-Day-Schwachstellen in Kühlungssteuerungen veröffentlicht", version 1.1, 17 November 2026 (in German): bsi.bund.de
This article is general guidance, not legal advice. Check the details against Directive (EU) 2022/2555 (NIS2) and your national law.